Actuators
Electromotoric actuators for air dampers or for fuel / air ratio control with oil or gas burners of small to medium capacity.
Use
The actuators are used primarily for controlling the amount of combustion air:
– Load-dependent in connection with P-PI or PID controllers, such as the RWF40…
– Directly with the help of the different types of burner controls, such as the LOA…, LMO…, LMG… or LFL…
Actuator
Mains voltage: AC 220 V -15 %…AC 240 V +10 %
Mains frequency: 50…60 Hz ±6 %
Type of motor: synchronous motor
Power consumption: 6.5 VA
Angular position: max. 160°
Mounting position: optional
Degree of protection: IP 40 to DIN 40050, provided adequate cable entries and screws are used
Cable entry: suited for 1 x Pg9 and 1 x Pg11, no locknut required
Cable connections: screw terminals for wires having a cross-sectional area of 0.5 to 2.5 mm²
Ferrules: matching the dia. of the standard wire
Direction of rotation: refer to «Type summary» in data sheet
Torques and holding torques: refer to «Type summary» in data sheet
Running times: 4.5…120 s for 90°
Coupling: drive shaft / geartrain by means of a pin
Weight (on average): approx. 800 g







There are no reviews yet.