Application
The automatic burner control units are suitable for the ignition and control of gas burners in gas firing installations of all types. For the flame control by means of ionisation probe or UV-cell. With ionisation control, an earthed mains is required.
These controls have been specially designed for industrial applications with a high switching frequency and a long life; e.g. the ignition transformer is switched on by means of a semi-conductor switch.
Features
– Flame control by means of ionisation electrode or UV-cell
– With prolonged reaction time
– Flame simulation check before starting
– Can directly replace the control IFS 137 without any re-wiring
– Remote reset and external fault indication
– Modern technique using semi-conductors
Mains voltage: 220/240 VAC 50/60 Hz
Safety time: 5s
Remote reset: Yes
Power consumption: approx. 18 VA
Reaction time: < 1 s
Number of valves: 2
Ambient temperature: -20 °C to +60 °C
Protective grade: IP 40
Fitting position: Arbitrary
Weight: 340 g
For more information on technical data, please refer to the data sheet.