Dark Light

LME11.230C2 – Control Box


Type: LME11.230C2

Use: For 1-stage burners

Flame detection: Ionization probe

Mains voltage: 230V~ 50-60Hz

Prepurge time (t1): 20 sec. min.

Safety time (TSA): 3 s max.

Plug-in base: AGK11

Brand: Siemens

Stock: Subject to availability

Price: Available on request

Plug-in base: Ordered separately.

 0

Compare

LME…

Burner controller for the supervision of 1- or 2-stage gas burners or gas burners of small to medium capacity, with or without fan in intermittent operation.

Flame detector: Ionization probe

Mains voltage: 230V~ 50-60Hz

Waiting time (tw): 2.5 sec. approx.

Prepurge time (t1): 20 sec. min.

Safety time (TSA): 3 s max.

Power consumption: 12 VA

Plug-in base: AGK11

Weight: Approx. 160 g without plug-in base

Operation temperature range: -20…+60 °C

For more information on technical data, please see data sheet.