Application
The flame detectors are used for the supervision of gas flames, yellow- or blue-burning oil flames and for ignition spark proving.
Function
With this type of flame supervision, the UV radiation emitted by gas or oil flames is used to generate the flame signal.
The radiation detector consists of a UV-sensitive cell with 2 electrodes, which ignite when illuminated with radiation in the 190…270 nm range of the spectrum, thereby triggering a current in the flame detector circuit.
The UV cell does not respond to glowing firebrick in the combustion chamber, daylight or light from the boiler room illumination.
Higher ambient temperatures reduce considerably the cell’s life.
For use with burner controls: LGB2… / LGB4… with AGQ1… LFL… LFE1… LFE10… LMG… with AGQ2… LME21… / LME22… / LME39… with AGQ3… LMV2… / LMV3… LMV5… with AGQ1…
Operating mode: Intermittent
Senstivity: Normal
Mechanical design: Die-cast aluminium housing
Degree of protection: IP 54
Mounting position: optional
Weight: approx. 740 g
Temperature range: -20…+60 °C
Humidity: < 95 % r.h.
For more technical information, please see data sheet.