LMO14
Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Maximum oil throughput up to 30 kg/h.
Use
The LMO… are designed for the startup and supervision of 1- or 2-stage forced draft oil burners in intermittent operation. Yellow-burning flames are supervised with photo resistive detectors QRB…, blue-burning flames with blue-flame detectors QRC… In terms of housing dimensions, electrical connections and flame detectors, the LMO… are identical with the LOA… oil burner controls.
General unit data
Mains voltage: AC 230 V -15 / +10 %
Mains frequency: 50…60 Hz ±6 %
External primary fuse (Si): 6.3 A (slow)
Power consumption: 12 VA
Waiting time (tw): 2.5 seconds max.
Ignition safety time (TSA): 10 seconds max.
Fuel valve stages: 1
Burner capacity: <30 kg/h
Flame supervision with: QRB…, QRC…
Mounting orientation: No restrictions
Temperature range: -20…+60 °C
Humidity: < 95 % r.h.
Weight: Approx. 200 g
For more information on technical data, please see data sheet.