Application
Differential pressure monitoring in firing, ventilation and air-conditioning systems. The AA-A2… can be used as a pressure, vacuum or differential pressure switch for air and non-aggressive gases. Not suitable for natural gas, propane, butane and other combustable gases.
Specifications
Setting range: 0.40 – 4.00 in. W.C (1 – 10 mbar)
Max. operating pressure: 7 psi (500 mbar)
Pressure connection: Threaded
Temperature range: -40 °C to +60 °C
Materials:
Housing: Polycarbonat
Switch: Polycarbonat
Diaphragms: NBR-based rubber
Switching contact: Silver (Ag)
Current rating: AC 5A resistive @ 120 VAC
Electrical connection: Screw terminals via 1/2″ NPT conduit connection.
Enclosure rating: NEMA Type 4