Technical description
The pressure switch GW…A6 is adjustable compact pressure switch as per EN for firing systems.
They are suited for switching a circuit on, off or over if the actual pressure value changes compared to the setpoint.
The setpoint (switching point) is set on an adjusting wheel with scale. A test nipple is integrated in the metal housing as standard.
Application
Pressure monitoring in combustion, ventilation and air-conditioning technologies. Suitable for gases of families 1,2,3 and other neutral gaseous media.
Specifications
Max. operating pressure: 500 mbar (50 kPa)
Pressure connection (Standard): Centrally on housing bottom, G 1/4 inner thread as per ISO 228
Measuring connection: Test nipple integrated in metal housing ø9
Ambient temperature: -15 °C to +70 °C
Medium temperature: -15 °C to +70 °C
Storage temperature: -30 °C to +80 °C
Materials
Housing: Aluminium die cast
Switch part: Polyamide
Diaphragms: NBR
Switching contact: Ag
For more information on technical data, please refer to the data sheet.