Technical description
The GW…A4 pressure switches are adjustable pressure switches for automatic burner controls. They are suitable for switching a circuit on, off or over on changes in actual pressure value relative to the set reference value. The reference value (switching point) is adjusted on a setting wheel provided with a scale. Test nipple integrated in metal housing as standard.
Application
Pressure monitoring in firing, ventilation and air-conditioning systems. Suitable for gases of families 1, 2, 3 and other neutral gaseous media.
Specifications
Setting range: 1 – 10 mbar
Max. operating pressure: 500 mbar (50 kPa)
Pressure connection: G 1/4 internal thread on center of housing underside as per ISO 228
Ambient temperature: -15 °C to +60 °C
Medium temperature: -15 °C to +60 °C
Storage temperature: -30 °C to +80 °C
Materials
Housing: Aluminium die cast
Switch part: Polyamide
Diaphragms: NBR
Switching contact: Ag
For more information on technical data, please refer to the data sheet.






There are no reviews yet.